Leave Your Message

News

Heat Stress Protection Upgrade: Plant-Scale WBGT Monitoring System Safeguards Worker Health
News

Heat Stress Protection Upgrade: Plant-Scale WBGT Monitoring System Safeguards Worker Health

2026-09-20

Heat Stress Protection Upgrade: Plant-Scale WBGT Monitoring System Safeguards Worker Health

JT Technology Delivers Integrated Real-Time WBGT Monitoring, On-Site Alarm, and Centralized Control for Industrial Heat Stress Prevention

Factory production environments include both indoor high-temperature workshops and outdoor open-air work areas. In summer, high temperatures combined with high humidity create significant safety risks such as heatstroke and fatigue-induced errors. High temperatures also affect equipment stability and reduce production efficiency. To strictly comply with national regulations including GBZ/T 189.7-2007 Measurement of Physical Factors in Workplace — Part 7: High Temperature and Classification of Occupational Exposure to Heat Stress, JT Technology has developed a comprehensive plant-scale WBGT monitoring and early warning system that precisely measures thermal environments in work zones and provides real-time high-temperature risk alerts.

The entire system uses a local wireless LAN transmission architecture without routing data through third-party cloud platforms, ensuring full data security. Monitoring data is aggregated in real time to the central control room, and each terminal supports customizable threshold-based audible and visual alarms, creating an integrated "real-time on-site monitoring, immediate local warning, centralized central control" heat stress prevention system.

ScreenShot_2026-09-20_134808_857 (2).png

Applicable Standards

  • GBZ/T 189.7-2007 — Measurement of Physical Factors in Workplace, Part 7: High Temperature
  • GBZ 2.2-2019 — Occupational Exposure Limits for Hazardous Factors in Workplace, Part 2: Physical Factors
  • GBZ/T 229.3-2025 — Classification of Occupational Hazards, Part 3: Heat Stress Work
  • AQ/T 4275-2016 — Technical Specifications for Prevention and Control of Occupational Heat Hazards
  • Administrative Measures for Heat Prevention and Cooling (National Health Commission)

System Objectives

  • Full-Coverage Monitoring: Real-time, precise collection of WBGT index, temperature, and humidity at key points across indoor production workshops and outdoor work areas.
  • Dual-End Warning: On-site audible and visual alarms at each monitoring point immediately alert workers when thresholds are exceeded, while the central control platform simultaneously triggers pop-up alerts.
  • Wireless Centralized Management: All monitoring data is transmitted reliably via wireless LAN, with unified aggregation, storage, query, and analysis at the central control room.
  • Compliance and Traceability: Automatically retained monitoring data supports occupational health inspections, safety production audits, and traceability requirements.

System Architecture

The system adopts a three-tier architecture — front-end collection layer, wireless transmission layer, and central control layer — designed for simplicity, stability, and ease of maintenance across complex indoor and outdoor factory environments.

  • Front-End Collection Layer: Nine industrial-grade WBGT monitoring terminals (3 outdoor, 6 indoor) that continuously collect WBGT index, ambient temperature, and relative humidity at each point. Each unit includes an on-board audible and visual alarm module with local threshold triggering.
  • Wireless Transmission Layer: LoRa wireless communication between each monitoring terminal and data acquisition unit eliminates the need for cabling. Real-time monitoring data, device status, and alarm information are transmitted to the central control host.
  • Central Control Layer: Comprising the central monitoring host, display terminal, and data storage software, this layer provides centralized data aggregation, real-time display, data storage, historical query, exceedance statistics, and remote parameter configuration.

bde2dc65-1eae-4088-93e6-f3b93e796838.png

Key Features

  • Wireless Deployment: Fully wireless transmission eliminates the need for trenching and cabling, minimizing installation time, avoiding production disruption, and allowing flexible point adjustment.
  • Dual Alarm Mechanism: On-site audible/visual alarms combined with remote central platform warnings ensure high-temperature risks are addressed promptly.
  • Precision and Compliance: Points are positioned at standard heights per national standards, with measurement accuracy meeting occupational health testing requirements.
  • Reliable and Rugged: Industrial-grade equipment is dust-proof, moisture-proof, and interference-resistant, suitable for high-dust, high-humidity workshops and outdoor weather exposure.

Measurement Point Layout

Point placement strictly follows national standards, prioritizing areas where workers concentrate, near heat sources, in poorly ventilated zones, and in high-temperature-prone areas. Monitoring height: 1.5 m for standing work, 1.1 m for seated work.

Outdoor Monitoring Points (Example): Designed for open-air work zones, material storage yards, and equipment maintenance areas.

  • Outdoor Point 1: Main open-air loading/unloading and transfer yard (no shade, high solar radiation).
  • Outdoor Point 2: Outdoor equipment maintenance area (combined equipment heat dissipation + solar exposure, frequent worker traffic).
  • Outdoor Point 3: Perimeter open-air passage and temporary work zones (covers scattered outdoor work, fills monitoring gaps).

Outdoor units use waterproof, dustproof, sun-protective industrial enclosures mounted on poles to avoid obstruction and ensure accurate sensor readings.

Indoor Monitoring Points (Example): Covering production workshops and process work zones, focused on areas with heat sources, poor ventilation, and dense occupancy.

  • Indoor Point 1: Workshop 1 heat source core area (concentrated equipment heat generation, elevated temperature and humidity).
  • Indoor Point 2: Workshop 1 poorly ventilated zone (dead corners with poor air circulation, heat accumulation).
  • Indoor Point 3: Workshop 2 assembly line area (dense occupancy, prolonged continuous work).
  • Indoor Point 4: Workshop 2 equipment heat dissipation zone (large production equipment radiating heat, localized high temperatures).
  • Indoor Point 5: Auxiliary material processing workshop high-temperature/high-humidity zone (process generates both heat and moisture, high stuffiness risk).
  • Indoor Point 6: Workshop transfer corridors and auxiliary work zones (covers scattered indoor points for full workshop coverage).

Indoor units use wall-mount or bracket installation, positioned away from direct equipment airflow and heat sources to ensure objective measurements.

e94c28c0-c5a2-4843-9720-178744072f8a.png

WBGT Monitoring Terminal Specifications

All terminals integrate wet-bulb, globe, air temperature, and humidity sensors, support automatic WBGT calculation, and include local audible and visual alarms. Key parameters:

  • Measured Parameters: WBGT index, ambient temperature, relative humidity.
  • Accuracy: WBGT ±0.5°C; Temperature ±0.5°C; Humidity ±3%RH.
  • Range: WBGT 0–60°C; Temperature -20 to 80°C; Humidity 0–100%RH.
  • Alarm Function: Customizable thresholds (per national heat stress classification standards); high-brightness light + buzzer alarm upon exceedance to prompt personnel to take shelter or stop work for cooling.
  • Communication: Built-in LoRa wireless module for real-time data transmission to the control room.
  • Protection Rating: Indoor units IP54 (dust/moisture resistant); Outdoor units IP65 (water/sun/lightning protected).
  • Power Supply: 220V AC or solar power.

d0e9f463-d104-42fd-9f1e-80554cf0adda.png

WBGT Central Monitoring Platform

  • Data Aggregation Display: Real-time display of all 9 monitoring points including ID, location, WBGT value, temperature, humidity, device status, and alarm status, with clear indoor/outdoor separation.
  • Exceedance Alerts: Automatic pop-up alerts and audible/visual notifications when any point exceeds thresholds; records alarm time, location, and exceeded value.
  • Data Storage and Traceability: Continuous automated data storage with retention ≥2 years; supports historical data query, trend charts, and report export.
  • Remote Configuration: Central control can remotely adjust alarm thresholds and data upload frequency for each point without on-site visit.
  • Device Status Monitoring: Real-time monitoring of terminal online/offline/fault status, with timely alerts for maintenance.

36af7206-bd31-4b83-97ec-6ee4f968c5d0.png

Data Management

The platform supports real-time data viewing, historical data review, automatic daily/weekly/monthly report generation, and data export/printing. Outputs can be directly used for factory safety self-inspection, occupational health testing, and regulatory audits — fully meeting compliance management requirements.