News
Heat Stress Protection Upgrade: Plant-Scale WBGT Monitoring System Safeguards Worker Health
Heat Stress Protection Upgrade: Plant-Scale WBGT Monitoring System Safeguards Worker Health
Factory production environments include both indoor high-temperature workshops and outdoor open-air work areas. In summer, high temperatures combined with high humidity create significant safety risks such as heatstroke and fatigue-induced errors. High temperatures also affect equipment stability and reduce production efficiency. To strictly comply with national regulations including GBZ/T 189.7-2007 Measurement of Physical Factors in Workplace — Part 7: High Temperature and Classification of Occupational Exposure to Heat Stress, JT Technology has developed a comprehensive plant-scale WBGT monitoring and early warning system that precisely measures thermal environments in work zones and provides real-time high-temperature risk alerts.
The entire system uses a local wireless LAN transmission architecture without routing data through third-party cloud platforms, ensuring full data security. Monitoring data is aggregated in real time to the central control room, and each terminal supports customizable threshold-based audible and visual alarms, creating an integrated "real-time on-site monitoring, immediate local warning, centralized central control" heat stress prevention system.

Applicable Standards
- GBZ/T 189.7-2007 — Measurement of Physical Factors in Workplace, Part 7: High Temperature
- GBZ 2.2-2019 — Occupational Exposure Limits for Hazardous Factors in Workplace, Part 2: Physical Factors
- GBZ/T 229.3-2025 — Classification of Occupational Hazards, Part 3: Heat Stress Work
- AQ/T 4275-2016 — Technical Specifications for Prevention and Control of Occupational Heat Hazards
- Administrative Measures for Heat Prevention and Cooling (National Health Commission)
System Objectives
- Full-Coverage Monitoring: Real-time, precise collection of WBGT index, temperature, and humidity at key points across indoor production workshops and outdoor work areas.
- Dual-End Warning: On-site audible and visual alarms at each monitoring point immediately alert workers when thresholds are exceeded, while the central control platform simultaneously triggers pop-up alerts.
- Wireless Centralized Management: All monitoring data is transmitted reliably via wireless LAN, with unified aggregation, storage, query, and analysis at the central control room.
- Compliance and Traceability: Automatically retained monitoring data supports occupational health inspections, safety production audits, and traceability requirements.
System Architecture
The system adopts a three-tier architecture — front-end collection layer, wireless transmission layer, and central control layer — designed for simplicity, stability, and ease of maintenance across complex indoor and outdoor factory environments.
- Front-End Collection Layer: Nine industrial-grade WBGT monitoring terminals (3 outdoor, 6 indoor) that continuously collect WBGT index, ambient temperature, and relative humidity at each point. Each unit includes an on-board audible and visual alarm module with local threshold triggering.
- Wireless Transmission Layer: LoRa wireless communication between each monitoring terminal and data acquisition unit eliminates the need for cabling. Real-time monitoring data, device status, and alarm information are transmitted to the central control host.
- Central Control Layer: Comprising the central monitoring host, display terminal, and data storage software, this layer provides centralized data aggregation, real-time display, data storage, historical query, exceedance statistics, and remote parameter configuration.

Key Features
- Wireless Deployment: Fully wireless transmission eliminates the need for trenching and cabling, minimizing installation time, avoiding production disruption, and allowing flexible point adjustment.
- Dual Alarm Mechanism: On-site audible/visual alarms combined with remote central platform warnings ensure high-temperature risks are addressed promptly.
- Precision and Compliance: Points are positioned at standard heights per national standards, with measurement accuracy meeting occupational health testing requirements.
- Reliable and Rugged: Industrial-grade equipment is dust-proof, moisture-proof, and interference-resistant, suitable for high-dust, high-humidity workshops and outdoor weather exposure.
Measurement Point Layout
Point placement strictly follows national standards, prioritizing areas where workers concentrate, near heat sources, in poorly ventilated zones, and in high-temperature-prone areas. Monitoring height: 1.5 m for standing work, 1.1 m for seated work.
Outdoor Monitoring Points (Example): Designed for open-air work zones, material storage yards, and equipment maintenance areas.
- Outdoor Point 1: Main open-air loading/unloading and transfer yard (no shade, high solar radiation).
- Outdoor Point 2: Outdoor equipment maintenance area (combined equipment heat dissipation + solar exposure, frequent worker traffic).
- Outdoor Point 3: Perimeter open-air passage and temporary work zones (covers scattered outdoor work, fills monitoring gaps).
Outdoor units use waterproof, dustproof, sun-protective industrial enclosures mounted on poles to avoid obstruction and ensure accurate sensor readings.
Indoor Monitoring Points (Example): Covering production workshops and process work zones, focused on areas with heat sources, poor ventilation, and dense occupancy.
- Indoor Point 1: Workshop 1 heat source core area (concentrated equipment heat generation, elevated temperature and humidity).
- Indoor Point 2: Workshop 1 poorly ventilated zone (dead corners with poor air circulation, heat accumulation).
- Indoor Point 3: Workshop 2 assembly line area (dense occupancy, prolonged continuous work).
- Indoor Point 4: Workshop 2 equipment heat dissipation zone (large production equipment radiating heat, localized high temperatures).
- Indoor Point 5: Auxiliary material processing workshop high-temperature/high-humidity zone (process generates both heat and moisture, high stuffiness risk).
- Indoor Point 6: Workshop transfer corridors and auxiliary work zones (covers scattered indoor points for full workshop coverage).
Indoor units use wall-mount or bracket installation, positioned away from direct equipment airflow and heat sources to ensure objective measurements.

WBGT Monitoring Terminal Specifications
All terminals integrate wet-bulb, globe, air temperature, and humidity sensors, support automatic WBGT calculation, and include local audible and visual alarms. Key parameters:
- Measured Parameters: WBGT index, ambient temperature, relative humidity.
- Accuracy: WBGT ±0.5°C; Temperature ±0.5°C; Humidity ±3%RH.
- Range: WBGT 0–60°C; Temperature -20 to 80°C; Humidity 0–100%RH.
- Alarm Function: Customizable thresholds (per national heat stress classification standards); high-brightness light + buzzer alarm upon exceedance to prompt personnel to take shelter or stop work for cooling.
- Communication: Built-in LoRa wireless module for real-time data transmission to the control room.
- Protection Rating: Indoor units IP54 (dust/moisture resistant); Outdoor units IP65 (water/sun/lightning protected).
- Power Supply: 220V AC or solar power.

WBGT Central Monitoring Platform
- Data Aggregation Display: Real-time display of all 9 monitoring points including ID, location, WBGT value, temperature, humidity, device status, and alarm status, with clear indoor/outdoor separation.
- Exceedance Alerts: Automatic pop-up alerts and audible/visual notifications when any point exceeds thresholds; records alarm time, location, and exceeded value.
- Data Storage and Traceability: Continuous automated data storage with retention ≥2 years; supports historical data query, trend charts, and report export.
- Remote Configuration: Central control can remotely adjust alarm thresholds and data upload frequency for each point without on-site visit.
- Device Status Monitoring: Real-time monitoring of terminal online/offline/fault status, with timely alerts for maintenance.

Data Management
The platform supports real-time data viewing, historical data review, automatic daily/weekly/monthly report generation, and data export/printing. Outputs can be directly used for factory safety self-inspection, occupational health testing, and regulatory audits — fully meeting compliance management requirements.

Sensor
Measuring Instruments
Measurement Systems